Home Contact Downloads Impressum

DTTHL 100/10

Capacity (kVA): 100 Primary voltage (kV): 10 Um1 (kV): 12
Secondary voltage (kV): 0,4 Um2 (kV): 1,1 Connection group: Dyn5
PO (W): 320 Pk 75 °C (W): 1750 Pk 120 °C (W): 2000
uk %: 4 Lp (A) (dB): 40 Lw (A) (dB): 51
Total weight(kg): 550 Total length (mm) A: 920 Total width Transformer (mm) C: 670
Total height (mm) B: 1050 Distance core centre LV
bars (mm) D:
170
Distance core centre HV voltage bars (mm) E: 240
Centre distance of rollers (mm) K: 520 Total width of undercarriage (mm): 670 Diameter of rollers (mm) M: 125
Width of rollers (mm): 40

Execution acc. to DIN 42 523 – Edition Dec. 93 HD 464.S2 Indoor installation E1; C2; F1 With tappings ±5 % connection group up to SN 100 kVA Yzn5 from SN > 100 kVA Dyn5

Version up to 1000 kVA

11 HV-terminal
12 LV-terminal,acc. to DIN 46206, Part 2
13 Earth connection DIN 48088-B-M12
14 Terminal strip for temperature control
21 Rating plate
22 Terminal marking plates acc. to DIN 42402
23 Warning plate VS 2 acc. to DIN 40008, Part 2
31 Roller form H acc. to DIN 42562, Part 1 (actually draft) for bidirectional movement
32 Lifting lugs
33 Hauling lugs for bi-directional shifting of the transformer
34 Fixing lugs for transport

Add inquiry Back to selection