Home Contact Downloads Impressum

DTTH 400/10

Capacity (kVA): 400 Primary voltage (kV): 10 Um1 (kV): 12
Secondary voltage (kV): 0,4 Um2 (kV): 1,1 Connection group: Dyn5
PO (W): 1150 Pk 75 °C (W): 4300 Pk 120 °C (W): 4900
uk %: 4 Lp (A) (dB): 56 Lw (A) (dB): 68
Total weight(kg): 1200 Total length (mm) A: 1260 Total width Transformer (mm) C: 820
Total height (mm) B: 1420 Distance core centre LV
bars (mm) D:
250
Distance core centre HV voltage bars (mm) E: 300
Centre distance of rollers (mm) K: 670 Total width of undercarriage (mm): 820 Diameter of rollers (mm) M: 125
Width of rollers (mm): 40

Execution acc. to DIN 42 523 – Edition Dec. 93 HD 464.S2 Indoor installation E1; C2; F1 With tappings ±5 % connection group up to SN 100 kVA Yzn5 from SN > 100 kVA Dyn5

Wicklungsmaterial AL

Version up to 1000 kVA

11 HV-terminal
12 LV-terminal,acc. to DIN 46206, Part 2
13 Earth connection DIN 48088-B-M12
14 Terminal strip for temperature control
21 Rating plate
22 Terminal marking plates acc. to DIN 42402
23 Warning plate VS 2 acc. to DIN 40008, Part 2
31 Roller form H acc. to DIN 42562, Part 1 (actually draft) for bidirectional movement
32 Lifting lugs
33 Hauling lugs for bi-directional shifting of the transformer
34 Fixing lugs for transport

Special execution / Accessories (optionally)
Standard enclosure for ground installation CZB-2
sheet steel enclosure, protection degree IP21, floor mounted, colour RAL7032, cable entrance from below, for indoor installation, bolted panels, delivered errected. Additional price for galvanised sheet is 20%, additional price for IP23: 100,- EUR, additional price for IP31: 50,- EUR. Outside dimension: 1700 mm length x 1100 mm width x 1700 mm height

Add inquiry Back to selection