DTTHM 400/10
|
|
Capacity (kVA):
400 |
Primary voltage (kV):
10 |
Um1 (kV):
12 |
|
Secondary voltage (kV):
0,4 |
Um2 (kV):
1,1 |
Connection group:
Dyn5 |
|
PO (W):
730 |
Pk 75 °C (W):
4300 |
Pk 120 °C (W):
4880 |
|
uk %:
4 |
Lp (A) (dB):
38 |
Lw (A) (dB):
51 |
|
Total weight(kg):
1300 |
Total length (mm) A:
1350 |
Total width Transformer (mm) C:
820 |
|
Total height (mm) B:
1280 |
Distance core centre LV bars (mm) D:
250 |
Distance core centre HV voltage bars (mm) E:
300 |
|
Centre distance of rollers (mm) K:
670 |
Total width of undercarriage (mm):
820 |
Diameter of rollers (mm) M:
125 |
|
Width of rollers (mm):
40 |
|
|
|
Execution acc. to DIN 42 523 – Edition Dec. 93 HD 464.S2 Indoor installation E1; C2; F1
With tappings ±5 % connection group up to SN 100 kVA Yzn5 from SN > 100 kVA Dyn5
Wicklungsmaterial AL
|
Version up to 1000 kVA
|
|
11 HV-terminal
12 LV-terminal,acc. to DIN 46206, Part 2
13 Earth connection DIN 48088-B-M12
14 Terminal strip for temperature control
21 Rating plate
22 Terminal marking plates acc. to DIN 42402
23 Warning plate VS 2 acc. to DIN 40008, Part 2
31 Roller form H acc. to DIN 42562, Part 1 (actually draft) for bidirectional movement
32 Lifting lugs
33 Hauling lugs for bi-directional shifting of the transformer
34 Fixing lugs for transport
|
|
Special execution / Accessories (optionally) Standard enclosure for ground installation CZB-2 sheet steel enclosure, protection degree IP21, floor mounted, colour RAL7032, cable entrance from below, for indoor installation, bolted panels, delivered errected. Additional price for galvanised sheet is 20%,
additional price for IP23: 100,- EUR,
additional price for IP31: 50,- EUR.
Outside dimension: 1700 mm length x 1100 mm width x 1700 mm height
|
|
|
|
|
 |
|