DOTUL 100 / 10
|
|
Capacity
(kVA):
100 |
Total
weight (kg):
680 |
Primary
voltage (kV):10 |
|
Um1 (kV):
12 |
PO (W):
210 |
Pk 75 °C (W):
1475 |
|
Total
length (mm):
930 |
Total
width (mm):
670 |
Total
height (mm):
1330 |
|
uk %:
4 |
Lp (A) (dB):
35 |
Oil mass(kg):
140 |
|
Execution acc. to DIN 42 500 (HD 428.1 S1)
Hermetic design, for outdoor installation with HV porcelain bushings
Max. ambient temperature 40 ºC, max. installation height 1000 m above sea level
Routine test acc to VDE 0532
max. system voltage HV: 24 kV / max. system voltage LV: 1,1 kV
Deviating parameters resp deviating design (e.g. conservator design)
on request deliverable with deviating dimensions and masses.
|
Hermetic design DIN 42500  |
|
11 HV bushings acc. to DIN 42531 in accordance with the series voltage DIN 43675 from 500 kVA
12 LV bushings acc. to DIN 42530 with flat terminal acc to
13 Earth connection BM 12 DIN 48088
21 Rating plate
22 Terminal marking plates
31 Bidirectional rollers DIN 42561
32 Lifting lugs also for active part including cover
33 Hauling lugs also for bi-directional shifting of the transformer
34 Hauling lugs
41 Oil drain device DIN 42551 up to 800 kVA A 22, from 1000 kVA A 31
42 Filling tube with female thread G 1½ A
61 Thermometer pocket T DIN 42554
91 Off-circuit tap changer for setting HV tappings
|
|
|
|
|
|
|
 |
|